Get a Quote
There is currently no image for this product.
Engine Generator Integrated Switchgear
Get A Quote
Specifications
Standard Equipment

Generator Protective Devices

ANSI Protective Devices
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices
(Utility Grade) SR-750 / SEL-351S, 25, 27/59, 81 O/U, 32,47 (Industrial Grade) 15

Environmental Parameters

Certifications
UL891
Control Panel Enclosure
NEMA1
Operating Temperature
0°C to 55°C
Storage Temperature
-20°C to 60°C

Technical Summary

Configuration
Floor Standing modular switchgear paralleling system (Master Breaker Panel for the first 2 gensets, separate structures for up to 8 additional gensets , utility, and load control/distribution)
Modes of Operation
Emergency Standby with redundant master control. Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application
LV only (208V - 480V)
  • Master Breaker Panel (MBP) for first 2 gensets
  • 12" Graphical Color Touchscreen display (HMI) Instant Auto Selector Switch
  • Spare inputs and outputs
  • Audible Alarm & Horn Silence Button
  • Emergency Stop Button for Each generator Top or Bottom Conduit Access (for MCP) for interconnect control wiring access